Page 21 - NG-1 1150, NG-1 1500, NG-1 2000, NG-1 3000 - Stand-Alone Nitrogen Generator System Installation Manual
P. 21
NOTE:
The TYCO Nitrogen Generator requires an in-line Air Maintenance Device (AMD) such as the TYCO AMD-1 which is equipped with an on-board field adjustable pressure regulator for each sprinkler system being served.
Air/Nitrogen Supply Line
Figure 3a
Dry Pipe/Preaction System Control Valve
Nitrogen Generator/Air Compressor
Step 6b: Plumb the Nitrogen/Air Supply Line – With Separate Air Compressor (Figure 3b)
A separate air compressor can be used as a back up to the nitrogen generator. In this application, the nitrogen/air discharge plumbing from the TYCO Nitrogen Generator and the separate air compressor are connected to the dry pipe or preaction valve trim with isolation ball valves in each supply line using a minimum 1⁄2” black steel, galvanized steel, or copper lines. The size of the nitrogen/air supply line must be based on both the length of pipe between the nitrogen generator and fire sprinkler systems and the total volume of fire sprinkler systems being supplied.
NOTE:
The TYCO Nitrogen Generator requires an in-line Air Maintenance Device (AMD) such as the TYCO AMD-1 which is equipped with an on-board field adjustable pressure regulator for each sprinkler system being served.
Air/Nitrogen Supply Line
Isolation Ball Valve
Isolation Ball Valve
Nitrogen Generator/Air Compressor
Air Supply Line
Air/Nitrogen Supply Line
Back-Up Air Compressor
Figure 3b
Dry Pipe/Preaction System Control Valve
TFP1275