Page 40 - NG-1 1150, NG-1 1500, NG-1 2000, NG-1 3000 - Stand-Alone Nitrogen Generator System Installation Manual
P. 40

Model EPS10-2 Pressure Switch Electrical Connections
Not Activated Activated BBBB
COM COM COM COM AAAA
              Switch 1 Switch 2
TYCO Remote Test Station (TRTI)
Terminal Strip Connections
Remote Test Station Operation Flowchart
Switch 1
Switch 2
            Depress Red LED Push-Button
     TILD ACTIVATED due to Corrosion
YES
RED LED NO Push-Button
Depress Amber LED Push-Button
  Illuminates
    CONTACT Johnson Controls
  TILD Operating Properly
YES
AMBER LED Push-Button Illuminates
NO
Replace Batteries
(2 x 2032 Batteries Required)
  Response to Device Activation
Activation of the pressure switch indicates that the thin wall section of the device has failed and the pressure chamber is exposed to system pressure. Contact Johnson Controls for instructions regarding replacement and testing of the failed In-Line Corrosion Detector.
TFP1275 Page 39 of 84
Re-Test TILD









































































   38   39   40   41   42