Page 43 - NG-1 1150, NG-1 1500, NG-1 2000, NG-1 3000 - Stand-Alone Nitrogen Generator System Installation Manual
P. 43
2. When connecting the TSGA Gas Analyzer to a fire sprinkler system using the TSV-D SMART Vent, the quick disconnect sampling port in the TSV-D must be removed and replaced with a 5/32” push- connect fitting.
Installation Instructions
1. Mount the TYCO SMART Gas Analyzer on a wall adjacent to the TAV-D Vent or the TSV-D SMART Vent (not included).
2. Once mounted, connect the 5/32” tubing to the push-connect fitting on the top of the TSGA.
3. Connect the opposite end of the tubing to the push-connect fitting on the outlet of the TAV-D or TSV-D Vent.
TYCO SMART Gas Analyzer with Dedicated TAV-D Dry Vent Assembly
5/32” Push Fitting
5/32” Tubing Between Vent and TSGA
5/32” Push Fitting
5/32” Tubing Between Vent and TSGA
Muffler to be Removed and Replaced with 5/32” Push Fitting
TYCO SMART Gas Analyzer with TSV-D Dry SMART Vent Assembly
Gas Sampling Port to be Removed and Replaced with 5/32” Push Fitting
TFP1275