Page 14 - NG-1 100, NG-1 250, NG-1 500 - Wall-Mounted Nitrogen Generator System Installation Manual
P. 14

Start-Up and Operational Procedures
INSTALLATION
Installation of the TYCO Nitrogen Generator requires five (5) steps: 1. Mount the cabinet in the appropriate location
2. Connect the dedicated power supply to the cabinet
3. Plumb the nitrogen/air supply line to the dry pipe and/or preaction sprinkler risers being served
with minimum 1⁄2” line
4. Plumb the condensate drain line to floor drain or building exterior
5. Connect nitrogen generator output signals to BMS or fire alarm system, where applicable
Wire Gauge Chart
1. Ensure an appropriately rated disconnect switch and circuit breaker (minimum 15 Amps and a SCCR of 5 kVA) are installed in a suitable and accessible location in accordance with the applicable national and/or local codes (i.e. NFPA 70).
2. The circuit breaker and disconnect are to be easily identifiable as associated with the equipment.
Ensure the ground wire is properly connected to the ground terminal(s) of the equipment using appropriately sized ground wire.
  Wire Gauge Chart
 Size
  Amperage
  Diameter
  Resistance
  (AWG)
   60° C (140° F)
   75° C (167° F)
   90° C (194° F)
   (Inches)
   (mm)
   (Ohms / 1,000 ft)
   (Ohms / km)
     18
16
14 15 12 20 10 30
8 36
15 15 20 20 30 30 43 48
.0403 1.024 6.385 .0508 1.291 4.016 .0641 1.628 2.525 .0808 2.053 1.588 .1019 2.588 .9989 .1285 3.264 .6282
20.95 13.17 8.282 5.211 3.277 2.061
                                                Step 1:
Mounting the nitrogen generator cabinet
The TYCO Nitrogen Generator is designed to be mounted directly to the wall at the appropriate location. Several factors should be considered in choosing the proper mounting location for the nitrogen generator:
· Access to required power supply (dedicated circuit)
· Access to sprinkler risers being supplied from nitrogen generator
· Access to drain for the condensate discharge line
· Clearance in front of the unit to open the cabinet door and for servicing the equipment · Cleanliness of the environment and air intake
CAUTION: Nitrogen generator cabinet includes ventilation vents in the bottom and side. Ensure that all ventilation vents are not blocked to allow proper ventilation throughout the nitrogen generator cabinet.
TFP1273
Page 13 of 80

























































   12   13   14   15   16