Page 39 - NG-1 100, NG-1 250, NG-1 500 - Wall-Mounted Nitrogen Generator System Installation Manual
P. 39

2. When connecting the TSGA Gas Analyzer to a fire protection system using the TSV-D SMART Vent, the quick disconnect sampling port in the TSV-D must be removed and replaced with a 5/32” push- connect fitting.
Installation Instructions
1. Mount the TYCO SMART Gas Analyzer on a wall adjacent to the TAV-D Manual Vent or the TSV-D SMART Vent (not included).
2. Once mounted, connect the 5/32” tubing to the push-connect fitting on the top of the TSGA.
3. Connect the opposite end of the tubing to the push-connect fitting on the outlet of the TAV-D or TSV-D Vent.
 TYCO SMART Gas Analyzer with TAV-D Dry Manual Vent Assembly
5/32” Push Fitting
 5/32” Tubing Between Vent and TSGA
     Muffler to be Removed and Replaced with 5/32” Push Fitting
  TYCO SMART Gas Analyzer with TSV-D Dry SMART Vent Assembly
5/32” Push Fitting
5/32” Tubing Between Vent and TSGA
      Gas Sampling Port to be Removed and Replaced with 5/32” Push Fitting
 TFP1273