Page 68 - NG-1 100, NG-1 250, NG-1 500 - Wall-Mounted Nitrogen Generator System Installation Manual
P. 68
VENT MAINTENANCE
TYCO Oxygen Removal Vents (TAV-D / TSV-D) Maintenance Instructions
1. TAV-D Vent - The TYCO TAV-D Vents must be inspected annually at minimum. While isolation ball valve is in the open position, check for air/water leaks and ensure the pressure gauge is displaying normal system pressure.
2. TSV-D SMART Vent - The TYCO TSV-D Vents must be inspected annually at minimum. While isolation ball valve is in the open position and the VENT button is illuminated, check for air/water leaks and ensure the pressure gauge is displaying normal system pressure.
3. TAV-D / TSV-D Vents - While isolation ball valve is in the closed position the inspection must include the condition of the in-line filter, and blockage in the “Y” strainer and restricted venting orifice. Depressurize the in-line filter housing by pressing the pressure relief valve on the bottom of the housing. Twist the filter housing counter-clockwise until it can be removed to expose the filter element.
4. TAV-D / TSV-D Vents - The filter element in the in-line filter should be replaced if a visual inspection reveals a significant collection of debris.
In-Line Filter Replacement Instructions
1. Close the isolation ball valve.
2. Depressurize the housing by pressing the pressure relief valve on the bottom of the in-line filter housing.
3. Remove the lower section of the in-line filter housing by turning the filter housing counterclockwise.
NOTE: A rubber o-ring/seal is located between the upper and lower sections of the filter housing.
4. Remove the old filter by turning the filter counterclockwise.
5. Replace with new filter. The filter is secured to the housing by turning the filter clockwise. NOTE: Ensure the filter is secured only finger/hand tight.
6. Install the rubber o-ring/seal on the lower section of the filter housing.
7. Re-install the filter housing by turning the filter housing clockwise.
NOTE: Ensure the filter housing is secured only finger/hand tight.
8. Open the isolation ball valve.
TFP1273