Page 9 - NG-1 100, NG-1 250, NG-1 500 - Wall-Mounted Nitrogen Generator System Installation Manual
P. 9

Nitrogen Quality
N2 Purity at Discharge: N2 Pressure at Discharge: N2 Water Dew Point:
FM Approved UL Listed
CE Certification
98% (maximum of 2.0% oxygen)
Min: 15 psig (1 bar); Max: feed air pressure minus 15 psig (1 bar) Less than -70°F (-57°C)
Standard 1035
508A Industrial Control Panel