Page 104 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 104

  102
OUTLET FITTINGS
 Figure 522 Sprinkler Outlet 1 of 2
                                                           D
BC
A E
                                                                                                             Nominal Pipe Size
 Outlet Size NPT or ISO 7-1 Pipe Threads
 Max.a Outlet End Load Lbs. (kN)
   Nominal Dimensions Inches (mm)
 Approx. Wgt. Lbs
(kg)
  Nominal Run Size ANSI Inches DN
  O.D. Inches (mm)
  A
 B
 C
  D
  E
  1
25
    1.315 (33,7)
   1/2
 165.9 (0,738)
   1.00 (25,4)
 3.40 (86,4)
   1.94 (49,3)
  0.56 (14,3)
  1.00 (25,4)
  0.9 (0,4)
 3/4
 259.9 (1,156)
 1.64 (41,7)
 3.40 (86,4)
 1.94 (49,3)
  1.14 (29,0)
  1.00 (25.4)
  1.1 (0,5)
 1
 259.9 (1,156)
 1.83 (46,5)
 3.40 (86,4)
 2.25 (57,2)
  1.26 (32,0)
  1.00 (25,4)
  1.1 (0,5)
  1-1/4
32
    1.660 (42,4)
   3/8
 165.9 (0,738)
 1.22 (31,0)
 3.78 (96,0)
 2.25 (57,2)
  0.91 (23,1)
  1.06 (26,9)
  0.9 (0,4)
 1/2
 165.9 (0,738)
 1.22 (31,0)
 3.78 (96,0)
 2.25 (57,2)
  0.78 (19,8)
  1.06 (26,9)
  0.9 (0,4)
 3/4
 259.9 (1,156)
 1.83 (46,5)
 3.78 (96,0)
 2.25 (57,2)
  1.33 (33,8)
  1.06 (26,9)
  1.1 (0,5)
 1
 406.9 (1,81)
 2.00 (50,8)
 3.78 (96,0)
 2.25 (57,2)
  1.44 (36,6)
  1.06 (26,9)
  1.3 (0,6)
  1-1/2
40
   1.900 (48,3)
  1/2
 165.9 (0,738)
 1.32 (33,5)
 4.00 (101,6)
 2.25 (57,2)
  0.88 (22,4)
  1.25 (31,8)
  1.1 (0,5)
 3/4
 259.9 (1,156)
 1.93 (49,0)
 4.00 (101,6)
 2.25 (57,2)
  1.43 (36,3
  1.25 (31,8)
  3.1 (0,5)
 1
 406.9 (1,81)
 2.11 (53,6)
 4.00 (101,6)
 2.25 (57,2)
  1.55 (39,4)
  1.25 (31,8)
  1.3 (0,6)
  2
50
    2.375 (60,3)
   1/2
 165.9 (0,738)
 1.56 (39,6)
 4.46 (113,3)
 2.25 (57,2)
  1.12 (28,4)
  1.50 (38,1)
  1.3 (0,6)
 3/4
 259.9 (1,156)
 2.17 (55,1)
 4.46 (113,3)
 2.25 (57,2)
  1.67 (42,4)
  1.50 (38,1)
  1.5 (0,7)
 1
  406.9 (1,81)
  2.35 (60,0)
  4.46 (113,3)
  2.50 (63,5)
   1.79 (45,5)
   1.50 (38,1)
   1.5 (0,7)
  a. Maximum pressure and end load are total from all loads based on standard weight steel pipe. Pressure ratings and end loads may differ on other pipe materials and/or wall thickness. Always confirm compatibility by contacting TYCO Fire Protection Products for details.
• Refer to Technical Data Sheet TFP1865 for more information.
   102   103   104   105   106