   Figure 522 Sprinkler Outlet 2 of 2
                                                           D
OUTLET FITTINGS 103 BC
A E
                                                                                                             Nominal Pipe Size
 Outlet Size NPT or ISO 7-1 Pipe Threads
 Max.a Outlet End Load Lbs. (kN)
   Nominal Dimensions Inches (mm)
 Approx. Wgt.
Lbs (kg)
  Nominal Run Size ANSI Inches (DN)
  O.D. Inches (mm)
  A
 B
 C
  D
  E
  2-1/2
65
   2.875 (73,0)
  1/2
 165.9 (0,738)
   2.00 (50,8)
 5.12 (130,0)
   2.25 (57,2)
  1.56 (39,6)
  1.69 (42,9)
  1.5 (0,7)
 3/4
 259.9 (1,156)
 2.50 (63,5)
 5.12 (130,0)
   2.25 (57,2)
  2.00 (50,8)
  1.69 (42,9)
  1.8 (0,8)
 1
 406.9 (1,81)
 2.70 (68,6)
 5.12 (130,0)
 2.50 (63,5)
  2.14 (54,4)
  1.69 (42,9)
  1.8 (0,8)
  76.1mm
65
    3.000 (76,1)
   1/2
 165.9 (0,738)
   2.00 (50,8)
 5.12 (130,0)
   2.25 (57,2)
  1.56 (39,6)
  1.82 (46,2)
  1.5 (0,7)
 3/4
 259.9 (1,156)
 2.50 (63,5)
 5.12 (130,0)
   2.25 (57,2)
  2.00 (50,8)
  1.82 (46,2)
  1.8 (0,8)
 1
  406.9 (1,81)
  2.75 (69,9)
  5.12 (130,0)
  2.50 (63,5)
   2.19 (55,6)
   1.82 (46,2)
   1.8 (0,8)
  a. Maximum pressure and end load are total from all loads based on standard weight steel pipe. Pressure ratings and end loads may differ on other pipe materials and/or wall thickness. Always confirm compatibility by contacting TYCO Fire Protection Products for details.
• Refer to Technical Data Sheet TFP1865 for more information.


























   103   104   105   106   107