Page 115 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 115
OUTLET FITTINGS 113
Figure 730 Threaded 10 of 10 Mechanical Tees & Crosses
DBC BC
ADA
E
FIGURE 730
TEE THREADED OUTLET
D
A
FIGURE 730
CROSS THREADED OUTLET
Nominal Run x Branch ANSI Inches DN
O.D. Inches (mm)
Hole Diameterb
Boltc Size Inches (mm)
Approx. Weight Lbs.
(kg)
Min. Inches (mm)
Max. Inches (mm)
Tee
Cross
8 x 2-1/2
200 x 65
8.625 x 2.875 (219,1 x 73,0)
2.75 (69,9)
2.88 (73,0)
3/4 x 4-3/4 (M20 x 121)
12.6 (5,7)
15.0 (6,8)
8 x 76,1mm
200 x 65
8.625 x 3.000 (219,1 x 76,1)
2.75 (69,9)
2.88 (73,0)
— (M20 x 121)
12.6 (5,7)
15.0 (6,8)
8 x3
200 x 80
8.625 x 3.500 (219,1 x 88,9)
3.50 (88,9)
3.63 (92,1)
3/4 x 4-3/4 (M20 x 121)
13.6 (6,1)
16.9 (7,7)
8 x4
200 x 100
8.625 x 4.500 (219,1 x 114,3)
4.50 (114,3)
4.63 (117,5)
3/4 x 4-3/4 (M20 x 121)
15.2 (6,9)
20.0 (9,1)
b. Proper outlet hole preparation is required for effective sealing and performance. Inspect the pipe seal surface within 5/8 inch (15,9 mm) of the hole to ensure it is free from conditions that would adversely affect proper gasket sealing. Remove any sharp or rough edges from the hole or upper housing contact area that might affect assembly, proper seating of the locating collar or flow from the outlet. For Mechanical Crosses, ensure double outlet holes are aligned on opposite sides of the pipe. The use of threaded components other than steel pipe, such as dry type sprinklers, etc., may not be compatible with the female threaded outlets of Mechanical Tees and Crosses. Always confirm compatibility by contacting your TYCO Fire Protection Products Technical Services representative.
c. Gold color coded metric bolt sizes are available upon request.