Page 118 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 118
116
OUTLET FITTINGS
Figure 730 Grooved 3 of 8 Mechanical Tees & Crosses
BC BC AA
E
A
FIGURE 730 FIGURE 730
TEE GROOVED OUTLET CROSS GROOVED OUTLET
Nominal Run x Branch ANSI Inches DN
O.D. Inches (mm)
Nominal Dimensions- Inches
(mm)
A
B
C
E
4 x2
100 x 50
4.500 x 2.375 (114,3 x 60,3)
4.00 (101,6)
7.13 (181,1)
4.06 (103,1)
2.78 (70,6)
4 x 2-1/2
100 x 65
4.500 x 2.875 (114,3 x 73,0)
4.00 (101,6)
7.13 (181,1)
4.38 (111,3)
2.78 (70,6)
4 x 76,1mm
100 x 65
4.500 x 3.000 (114,3 x 76,1)
4.00 (101,6)
7.13 (181,1)
4.38 (111,3)
2.78 (70,6)
4 x3
100 x 80
4.500 x 3.500 (114,3 x 88,9)
4.13 (104,9)
7.13 (181,1)
5.13 (130,3)
2.78 (70,6)
5 x 1-1/2
125 x 40
5.563 x 1.900 (141,3 x 48,3)
4.63 (117,6)
8.13 (206,5)
3.56 (90,4)
3.37 (85,6)
5 x2
125 x 50
5.563 x 2.375 (141,3 x 60,3)
4.63 (117,6)
8.13 (206,5)
4.06 (103,1)
3.37 (85,6)
5 x 2-1/2
125 x 65
5.563 x 2.875 (141,3 x 73,0)
4.75 (120,7)
8.13 (206,5)
4.38 (111,3)
3.37 (85,6)
5 x 76,1mm
125 x 65
5.563 x 3.000 (141,3 x 76,1)
4.75 (120,7)
8.13 (206,5)
4.38 (111,3)
3.37 (85,6)
5 x3
125 x 80
5.563 x 3.500 (141,3 x 88,9)
5.00 (127,0)
8.13 (206,5)
5.13 (130,3)
3.37 (85,6)
139,7mm x 1-1/2
125 x 40
5.500 x 1.900 (139,7 x 48,3)
4.63 (117,6)
8.13 (206,5)
3.56 (90,4)
3.37 (85,6)
139,7mm x 2
125 x 50
5.500 x 2.375 (139,7 x 60,3)
4.63 (117,6)
8.13 (206,5)
4.06 (103,1)
3.37 (85,6)
139,7mm x 2-1/2
125 x 65
5.500 x 2.875 (139,7 x 73,0)
4.75 (120,7)
8.13 (206,5)
4.38 (111,3)
3.37 (85,6)
139,7mm x 76,1mm
125 x 65
5.500 x 3.000 (139,7 x 76,1)
4.75 (120,7)
8.13 (206,5)
4.38 (111,3)
3.37 (85,6)
139,7mm x 3
125 x 80
5.500 x 3.500 (139,7 x 88,9)
5.00 (127,0)
8.13 (206,5)
5.13 (130,3)
3.37 (85,6)
• Pressure ratings are based on pipe schedule, pipe size, and approval agency. Approved pressure ratings start on page 152.
• Refer to Technical Data Sheet TFP1860 for more information.