OUTLET FITTINGS
Figure 730 Grooved 5 of 8 Mechanical Tees & Crosses
BC BC AA
E
A
FIGURE 730 FIGURE 730
TEE GROOVED OUTLET CROSS GROOVED OUTLET
Nominal Run x Branch ANSI Inches DN
O.D. Inches (mm)
Nominal Dimensions- Inches
(mm)
A
B
C
E
6 x 1-1/4
150 x 32
6.625 x 1.660 (168,3 x 42,2)
5.13 (130,3)
9.25 (235,0)
3.56 (90.4)
3.90 (99,1)
6 x 1-1/2
150 x 40
6.625 x 1.900 (168,3 x 48,3)
5.13 (130,3)
9.25 (235,0)
3.56 (90,4)
3.90 (99,1)
6 x2
150 x 50
6.625 x 2.375 (168,3 x 60,3)
5.13 (130,3)
9.25 (235,0)
4.06 (103,1)
3.90 (99,1)
6 x 2-1/2
150 x 65
6.625 x 2.875 (168,3 x 73,0)
5.13 (130,3)
9.25 (235,0)
4.38 (111,3)
3.90 (99,1)
6 x 76,1mm
150 x 65
6.625 x 3.000 (168,3 x 76,1)
5.13 (130,3)
9.25 (235,0)
4.38 (111,3)
3.90 (99,1)
6 x3
150 x 80
6.625 x 3.500 (168,3 x 88,9)
5.50 (139,7)
9.25 (235,0)
5.13 (130,3)
3.90 (99,1)
6 x4
150 x 100
6.625 x 4.500 (168,3 x 114,3)
5.38 (136,7)
9.25 (235,0)
6.13 (155,7)
3.90 (99,1)
165,1mm x 1-1/4
150 x 32
6.500 x 1.660 (165,1 x 42,2)
5.13 (130,3)
9.25 (235,0)
3.56 (90,4)
3.90 (99,1)
165,1mm x 1-1/2
150 x 40
6.500 x 1.900 (165,1 x 48,3)
5.13 (130,3)
9.25 (235,0)
3.56 (90,4)
3.90 (99,1)
165,1mm x 2
150 x 50
6.500 x 2.375 (165,1 x 60,3)
5.13 (130,3)
9.25 (235,0)
4.06 (103,1)
3.90 (99,1)
165,1mm x 2-1/2
150 x 65
6.500 x 2.875 (165,1 x 73,0)
5.13 (130,3)
9.25 (235,0)
4.38 (111,3)
3.90 (99,1)
165,1mm x 76,1mm
150 x 65
6.500 x 3.000 (165,1 x 76,1)
5.13 (130,3)
9.25 (235,0)
4.38 (111,3)
3.90 (99,1)
165,1mm x 3
150 x 80
6.500 x 3.500 (165,1 x 88,9)
5.50 (139,7)
9.25 (235,0)
5.13 (130,3)
3.90 (99,1)
165,mm x 4
150 x 100
6.500 x 4.500 (165,1 x 114,1)
5.38 (136,7)
9.25 (235,0)
6.13 (155,7)
3.90 (99,1)
• Pressure ratings are based on pipe schedule, pipe size, and approval agency. Approved pressure ratings start on page 152.
• Refer to Technical Data Sheet TFP1860 for more information.