Page 144 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 144

  142 APPROVED PRESSURE RATINGS
 Figure 707 Heavy-Duty Flexible Coupling 2 of 3
 Pipe1, 2 Schedule*
   Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
   O.D. Inches (mm)
  UL
   ULC
   FM
   VdS
   LPCB
  psi (bar)
  Schedule 40
   6
150
 6.625 (168,3)
   500 (34,5)
  500 (34,5)
  500 (34,5)
  —
  —
  Schedule 40
 8
200
 8.625 (219,1)
 500 (34,5)
  500 (34,5)
  500 (34,5)
  —
  —
 Schedule 40
 10
250
 10.750 (273,0)
 500 (34,5)
  500 (34,5)
  500 (34,5)
  —
  —
 Schedule 40
 12
300
 12.750 (323,9)
 500 (34,5)
  500 (34,5)
  500 (34,5)
  —
  —
 2.5 mm Wall Thickness
 —
65
 3.000 (76,1)
 300 (20,7)
  —
  —
  —
  —
 EN 10255 Heavy
 —
65
 3.000 (76,1)
 —
  —
  300 (20,7)
  —
  —
 EN 10255 Medium
 —
65
 3.000 (76,1)
 —
  —
  300 (20,7)
  —
  —
 5.0 mm Wall Thickness
 —
150
 6.500 (165,1)
 300 (20,7)
  —
  —
  —
  —
 EN 10255 Heavy
 —
150
 6.500 (165,1)
 —
  —
  300 (20,7)
  —
  —
 EN 10255 Medium
 —
150
 6.500 (165,1)
 —
  —
  300 (20,7)
  —
  —
 ISO 65 Medium
   1-1/2
40
 1.900 (48,3)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 2
50
 2.375 (60,3)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 —
65
 3.000 (76,1)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 3
80
 3.500 (88,9)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 4
100
 4.500 (114,3)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 —
150
 6.500 (165,1)
 —
  —
  —
  —
  290 (20)
 ISO 4200 Wall Thickness 5,4 mm
 6
150
  6.625 (168,3)
  —
   —
   —
   —
   290 (20)
 1. See Agency website for Listing/Approvals of other pipe specifications: UL Website - see Online Certification Directory, ww.ul.com
FM Global Website - www.approvalguide.com
2. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website - see Search Our Listings - Automatic Sprinklers, Water Spray and Deluge System, www.redbooklive.com.
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.
   142   143   144   145   146