Page 150 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 150
148 APPROVED PRESSURE RATINGS
Figure 71 Flange Adapter 2 of 2
Pipe3, 4 Schedule*
Nominal Pipe Size
Rated Pressure
ANSI Inches DN
O.D. Inches (mm)
UL
ULC
FM
VdS
LPCB
psi (bar)
EN 10255 Medium
—
125
5.500 (139,7)
—
—
250 (17,24)
—
—
EN 10255 Medium
—
150
6.500 (165,1)
250 (17,24)
—
250 (17,24)
—
—
ISO 65 Medium
2
50
2.375 (60,3)
—
—
—
—
290 (20)
ISO 65 Medium
—
65
3.000 (76,1)
—
—
—
—
290 (20)
ISO 65 Medium
3
80
3.500 (88,9)
—
—
—
—
290 (20)
ISO 65 Medium
4
100
4.500 (114,3)
—
—
—
—
290 (20)
ISO 65 Medium
—
150
6.500 (165,1)
—
—
—
—
290 (20)
ISO 4200 Wall Thickness 5,4 mm
6
150
6.625 (168,3)
—
—
—
—
290 (20)
ISO 4200 Wall Thickness 5,4 mm
8
200
8.625 (219,1)
—
—
—
—
290 (20)
ISO 4200 Wall Thickness 5,4 mm
10
250
10.750 (273,0)
—
—
—
—
290 (20)
ISO 4200 Wall Thickness 5,4 mm
12
300
12.750 (323,9)
—
—
—
—
232 (16)
DIN 2448 or 2548
2
50
2.375 (60,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
—
65
3.000 (76,1)
—
—
—
232 (16)
—
DIN 2448 or 2548
3
80
3.500 (88,9)
—
—
—
232 (16)
—
DIN 2448 or 2548
4
100
4.500 (114,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
—
125
5.500 (139,7)
—
—
—
232 (16)
—
DIN 2448 or 2548
6
150
6.625 (168,3)
—
—
—
232 (16)
—
3. See Agency website for Listing/Approvals of other pipe specifications: UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com
4. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website see Search Our Listings - Automatic Sprinklers, water Spray and Deluge Systems, www.redbooklive.com
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.