Page 150 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 150

  148 APPROVED PRESSURE RATINGS
 Figure 71 Flange Adapter 2 of 2
 Pipe3, 4 Schedule*
   Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
  O.D. Inches (mm)
   UL
   ULC
   FM
   VdS
   LPCB
  psi (bar)
  EN 10255 Medium
  —
125
  5.500 (139,7)
   —
  —
  250 (17,24)
  —
  —
 EN 10255 Medium
 —
150
 6.500 (165,1)
 250 (17,24)
  —
  250 (17,24)
  —
  —
 ISO 65 Medium
 2
50
 2.375 (60,3)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 —
65
 3.000 (76,1)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 3
80
 3.500 (88,9)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 4
100
 4.500 (114,3)
 —
  —
  —
  —
  290 (20)
 ISO 65 Medium
 —
150
  6.500 (165,1)
  —
   —
   —
   —
   290 (20)
  ISO 4200 Wall Thickness 5,4 mm
 6
150
 6.625 (168,3)
  —
 —
 —
 —
 290 (20)
 ISO 4200 Wall Thickness 5,4 mm
 8
200
 8.625 (219,1)
 —
  —
  —
  —
  290 (20)
 ISO 4200 Wall Thickness 5,4 mm
 10
250
 10.750 (273,0)
 —
  —
  —
  —
  290 (20)
 ISO 4200 Wall Thickness 5,4 mm
 12
300
 12.750 (323,9)
 —
  —
  —
  —
  232 (16)
 DIN 2448 or 2548
 2
50
 2.375 (60,3)
 —
  —
  —
  232 (16)
  —
 DIN 2448 or 2548
 —
65
 3.000 (76,1)
 —
  —
  —
  232 (16)
  —
 DIN 2448 or 2548
 3
80
 3.500 (88,9)
 —
  —
  —
  232 (16)
  —
 DIN 2448 or 2548
 4
100
 4.500 (114,3)
 —
  —
  —
  232 (16)
  —
 DIN 2448 or 2548
 —
125
 5.500 (139,7)
   —
  —
  —
  232 (16)
  —
 DIN 2448 or 2548
   6
150
   6.625 (168,3)
  —
   —
   —
   232 (16)
   —
 3. See Agency website for Listing/Approvals of other pipe specifications: UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com
4. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website see Search Our Listings - Automatic Sprinklers, water Spray and Deluge Systems, www.redbooklive.com
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.
   148   149   150   151   152