Page 151 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 151

  APPROVED PRESSURE RATINGS 149
 Figure 702 Male Threaded Outlet Coupling
 Pipe1 Sch.*
     Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
   O.D. Inches (mm)
  UL
   ULC
   FM
  VdS
  LPCB
  psi (bar)
   Schedule 10, 40
  2x 1
50 x 25
 2.375 x 1.315 (60,3 x 33,7)
   300 (20,7)
  300 (20,7)
  300 (20,7)
 —
   —
 Schedule 10, 40
  2-1/2 x 1-1/4
65 x 32
 2.875 x 1.660 (73,0 x 42,4)
 —
  —
  300 (20,7)
 —
 —
 Schedule 10, 40
  2-1/2 x 1-1/2
65 x 40
 2.875 x 1.900 (73,0 x 48,3)
 —
  —
  300 (20,7)
 —
 —
 Schedule 10, 40
  3x 1
80 x 25
 3.500 x 1.315 (88,9 x 33,7)
 300 (20,7)
  300 (20,7)
  300 (20,7)
 —
 —
 Schedule 10, 40
  3 x 1-1/2
80 x 40
 3.500 x 1.900 (88,9 x 48,3)
 —
  —
  300 (20,7)
 —
 —
 Schedule 10, 40
  4x 1
100 x 25
 4.500 x 1.315 (114,3 x 33,7)
 300 (20,7)
  300 (20,7)
  —
 —
 —
 Schedule 10, 40
  4 x 1-1/2
100 x 40
 4.500 x 1.900 (114,3 x 48,3)
 —
  —
  300 (20,7)
 —
 —
 Schedule 10, 40
  4x 2
100 x 50
 4.500 x 2.375 (114,3 x 60,3)
 —
  —
  300 (20,7)
 —
 —
 Schedule 10, 40
  6 x 1-1/2
150 x 40
 6.625 x 1.900 (168,3 x 48,3)
 300 (20,7)
  300 (20,7)
  300 (20,7)
 —
 —
 Schedule 10, 40
   6x 2
150 x 50
  6.625 x 2.375 (168,3 x 60,3)
  —
   —
   300 (20,7)
  —
  —
 1. See Agency website for Listing/Approvals of other pipe specifications: UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - ww.approvalguide.com
* See Pipe Schedule Key on pages 127-128.
   149   150   151   152   153