152 APPROVED PRESSURE RATINGS
Figure 730 Threaded Outlet 1 of 10
Pipe2, 3 Sch.*
Nominal Pipe Size
Rated Pressure
ANSI Inches DN
O.D. Inches (mm)
UL
ULC
FM
VdS
LPCB
psi (bar)
Sch. 10, 40
2 x 1/2
50 x 15
2.375 x 0.840 (60,3 x 21,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2 x 3/4
50 x 20
2.375 x 1.050 (60,3 x 26,7)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2 x1
50 x 25
2.375 x 1.315 (60,3 x 33,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2 x 1-1/4
50 x 32
2.375 x 1.600 (60,3 x 42,2)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2 x 1-1/2
50 x 40
2.375 x 1.900 (60,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2-1/2 x 1/2
65 x 15
2.875 x 0.840 (73,0 x 21,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2-1/2 x 3/4
50 x 20
2.875 x 1.050 (73,0 x 26,7)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2-1/2 x 1
50 x 25
2.875 x 1.315 (73,0 x 33,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2-1/2 x 1-1/4
50 x 32
2.875 x 1.600 (73,0 x 42,2)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2-1/2 x 1-1/2
50 x 40
2.875 x 1.900 (73,0 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
2-1/2 x 2
65 x 50
2.875 x 2.375 (73,0 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
3 x 1/2
80 x 15
3.500 x 0.840 (88,9 x 21,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
3 x 3/4
80 x 20
3.500 x 1.050 (88,9 x 26,7)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
3 x1
80 x 25
3.500 x 1.315 (88,9 x 33,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
3 x 1-1/4
80 x 32
3.500 x 1.660 (88,9 x 42,2)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
3 x 1-1/2
80 x 40
3.500 x 1.900 (88,9 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
3 x2
80 x 50
3.500 x 2.375 (88,9 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approvals of other pipe specifications:
UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com
3. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website - see Search Our Listing - Automatic Sprinklers, Water Spray and Deluge Systems, www.redbooklive.com
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.