Page 155 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 155
APPROVED PRESSURE RATINGS 153
Figure 730 Threaded Outlet 2 of 10
Pipe2, 3 Sch.*
Nominal Pipe Size
Rated Pressure
ANSI Inches DN
O.D. Inches (mm)
UL
ULC
FM
VdS
LPCB
psi (bar)
Sch. 10, 40
4 x 1/2
100 x 15
4.500 x 0.840 (114,3 x 21,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x 3/4
100 x 20
4.500 x 1.050 (114,3 x 26,7)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x1
100 x 2
4.500 x 1.315 (114,3 x 33,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x 1-1/4
100 x 32
4.500 x 1.660 (114,3 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x 1-1/2
100 x 40
4.500 x 1.900 (114,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x2
100 x 50
4.500 x 2.375 (114,3 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x 2-1/2
100 x 65
4.500 x 2.875 (114,3 x 73,0)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x 76,1
100 x 65
4.500 x 3.000 (114,3 x 76,1)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
4 x3
100 x 80
4.500 x 3.500 (114,3 x 88,9)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
5 x 1-1/2
125 x 40
5.563 x 1.900 (114,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
5 x2
125 x 50
5.563 x 2.375 (114,3 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
5 x 2-1/2
125 x 65
5.563 x 2.875 (114,3 x 73,0)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
5 x3
125 x 80
5.563 x 3.500 (114,3 x 88,9)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
6 x 1-1/4
150 x 40
6.625 x 1.660 (168,3 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
6 x 1-1/2
150 x 40
6.625 x 1.900 (168,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
6 x2
150 x 50
6.625 x 2.375 (168,3 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch. 10, 40
6 x 2-1/2
150 x 65
6.625 x 2.875 (168,3 x 73,0)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approvals of other pipe specifications:
UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com
3. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website - see Search Our Listing - Automatic Sprinklers, Water Spray and Deluge Systems, www.redbooklive.com
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.