  14 GENERAL INFORMATION
 Grinnell Grooved Fittings - Pressure Loss
 Friction Resistancea (Expressed as Equivalent Straight Pipe)
 Nominal Size ANSI Inches DN
  O.D. Inches (mm)
  Elbow
  Tee
 90° Feet (Meters)
  45° Feet (Meters)
  Branch Feet (Meters)
  Run
Feet (Meters)
 1-1/4
32
   1.60 (42,4)
  1.9 (0,6)
  1.0 (0,3)
  4.8 (1,5)
  1.9 (0,6)
 1-1/2
40
   1.90 (48,3)
  2.3 (0,7)
  1.2 (0,4)
  5.8 (1,8)
  2.3 (0,7)
 2
50
   2.38 (60,3)
  3.2 (1,0)
  1.6 (0,5)
  8.0 (2,5)
  3.2 (1,0)
 2-1/2
65
   2.88 (73,0)
  3.9 (1,2)
  2.0 (0,6)
  9.8 (3,0)
  3.9 (1,2)
  —
65
 3.00 (76,1)
  4.1 (1,2)
  2.1 (0,6)
  10.3 (3,1)
  4.1 (1,2)
 3
80
 3.50 (88,9)
  4.9 (1,5)
  2.4 (0,7)
  12.2 (3,7)
  4.9 (1,5)
 —
100
 4.25 (108,0)
  6.5 (2,0)
  3.3 (1,0)
  16.3 (5,0)
  6.5 (2,0)
 4
100
 4.50 (114,3)
  6.5 (2,0)
  3.3 (1,0)
  16.3 (5,0)
  6.5 (2,0)
 —
125
 5.25 (133,0)
  8.0 (2,4)
  4.0 (1,2)
  20.0 (6,1)
  8.0 (2,4)
 —
125
 5.50 (139,7)
  8.0 (2,4)
  4.1 (1,3)
  20.0 (6,1)
  8.0 (2,4)
 5
125
 5.56 (141,3)
  8.2 (2,5)
  4.1 (1,3)
  20.5 (6,3)
  8.2 (2,5)
 —
150
 6.25 (159,0)
  9.5 (2,9)
  4.8 (1,4)
  23.8 (7,2)
  9.5 (2,9)
 —
150
 6.50 (165,1)
  9.5 (2,9)
  4.8 (1,4)
  23.8 (7,2)
  9.5 (2,9)
 6
150
 6.63 (168,3)
  9.9 (3,0)
  5.0 (1,5)
  24.8 (7,6)
  9.9 (3,0)
 —
200
 8.50 (216,3)
  13.1 (4,0)
  6.6 (2,0)
  32.8 (10,0)
  13.1 (4,0)
 8
200
 8.63 (219,1)
  13.1 (4,0)
  6.6 (2,0)
  32.8 (10,0)
  13.1 (4,0)
 10
250
 10.75 (273,0)
  16.5 (5,0)
  8.3 (2,5)
  41.3 (12,6)
  16.5 (5,0)
 12
300
  12.75 (323,9)
   19.9 (6,1)
   9.9 (3,0)
   49.7 (15,1)
   19.9 (6,1)
 a. Friction resistance for all elbows and tees except Figures 510S and 519S.