Page 162 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 162

  160 APPROVED PRESSURE RATINGS
 Figure 730 Threaded Outlet 9 of 10
 Pipe2, 3 Sch.*
       Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
 O.D. Inches (mm)
   UL
   ULC
  FM
  VdS
   LPCB
  psi (bar)
   DIN 2448 or 2548
 60,3mm x 48,3mm
65 x 40
  2.375 x 1.900 (60,3 x 48,3)
   —
  —
 —
   232 (16)
  —
 DIN 2448 or 2548
 76,1mm x 21,3mm
65 x 15
 3.000 x 0.840 (73,0 x 21,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 76,1mm x 26,7mm
65 x 20
 3.000 x 1.050 (73,0 x 26,7)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 76,1mm x 33,7mm
65 x 25
 3.000 x 1.315 (73,0 x 33,7)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 76,1mm x 42,4mm
65 x 32
 3.000 x 1.660 (73,0 x 42,4)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 76,1mm x 48,3mm
65 x 40
 3.000 x 1.900 (73,0 x 48,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 76,1mm x 60,3mm
65 x 50
 3.000 x 2.375 (73,0 x 60,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 88,9mm x 21,3mm
80 x 15
 3.500 x 0.840 (88,9 x 21,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 88,9mm x 26,7mm
80 x 20
 3.500 x 1.050 (88,9 x 26,7)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 88,9mm x 33,7mm
80 x 25
 3.500 x 1.315 (88,9 x 33,7)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 88,9mm x 42,4mm
80 x 32
 3.500 x 1.660 (88,9 x 42,4)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 88,9mm x 48,3mm
80 x 40
 3.500 x 1.900 (88,9 x 48,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 88,9mm x 60,3mm
80 x 50
 3.500 x 2.375 (88,9 x 60,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 114,3mm x 21,3mm
100 x 15
 4.500 x 0.840 (114,3 x 21,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 114,3mm x 26,7mm
100 x 20
 4.500 x 1.050 (114,3 x 26,7)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 114,3mm x 33,7mm
100 x 25
 4.500 x 1.315 (114,3 x 33,7)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
  114,3mm x 42,4mm
100 x 32
  4.500 x 1.660 (114,3 x 42,4)
  —
   —
  —
  232 (16)
   —
 1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approvals of other pipe specifications:
UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com
3. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website - see Search Our Listing - Automatic Sprinklers, Water Spray and Deluge Systems, www.redbooklive.com
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.