Page 163 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 163

  APPROVED PRESSURE RATINGS 161
 Figure 730 Threaded Outlet 10 of 10
 Pipe2, 3 Sch.*
       Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
 O.D. Inches (mm)
   UL
   ULC
  FM
  VdS
   LPCB
  psi (bar)
   DIN 2448 or 2548
 114,3mm x 48,3mm
100 x 40
  4.500 x 1.900 (114,3 x 48,3)
   —
  —
 —
   232 (16)
  —
 DIN 2448 or 2548
 114,3mm x 60,3mm
100 x 50
 4.500 x 2.375 (114,3 x 60,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 114,3mm x 76,1mm
100 x 65
 4.500 x 3.000 (114,3 x 76,1)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 114,3mm x 88.9mm
100 x 80
 4.500 x 3.500 (114,3 x 88,9)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 168,3mm x 42,4mm
150 x 32
 6.625 x 1.660 (168,3 x 42,4)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 168,3mm x 48,3mm
150 x 40
 6.625 x 1.900 (168,3 x 48,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 168,3mm x 60,3mm
150 x 50
 6.625 x 2.375 (168,3 x 60,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 168,3mm x 76,1mm
150 x 65
 6.625 x 3.000 (168,3 x 76,1)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
 219,1mm x 60,3mm
200 x 50
 8.625 x 2.375 (219,1 x 60,3)
 —
  —
 —
 232 (16)
  —
 DIN 2448 or 2548
  219,1mm x 76,1mm
200 x 65
  8.625 x 3.000 (219,1 x 76,1)
  —
   —
  —
  232 (16)
   —
 1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approvals of other pipe specifications:
UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com
3. See Agency website for Listing/Approvals of other pipe specifications:
LPCB Website - see Search Our Listing - Automatic Sprinklers, Water Spray and Deluge Systems, www.redbooklive.com
VdS Website - see certifications, www.vds.de
* See Pipe Schedule Key on pages 127-128.