Page 164 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 164
162 APPROVED PRESSURE RATINGS
Figure 730 Grooved Outlet 1 of 7
Pipe2 Sch.*
Nominal Pipe Size
Rated Pressure
ANSI Inches DN
O.D. Inches (mm)
UL
ULC
FM
VdS
LPCB
psi (bar)
Sch 10, 40
2 x 1-1/4
50 x 32
2.375 x 1.660 (60,3 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
2 x 1-1/2
50 x 40
2.375 x 1.900 (60,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
2-1/2 x 1-1/4
65 x 32
2.875 x 1.660 (73,0 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
2-1/2 x 1-1/2
65 x 40
2.875 x 1.900 (73,0 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
2-1/2 x 2
65 x 50
2.875 x 2.375 (73,0 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
3 x 1-1/4
80 x 32
3.500 x 1.660 (88,9 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
3 x 1-1/2
80 x 40
3.500 x 1.900 (88,9 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
3x 2
80 x 50
3.500 x 2.375 (88,9 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
4 x 1-1/4
100 x 32
4.500 x 1.660 (114,3 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
4 x 1-1/2
100 x 40
4.500 x 1.900 (114,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
4x 2
100 x 50
4.500 x 2.375 (114,3 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
4 x 2-1/2
100 x 65
4.500 x 2.875 (114,3 x 73,0)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
4 x 76,1
100 x 65
4.500 x 3.000 (114,3 x 76,1)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
4x 3
100 x 80
4.500 x 3.500 (114,3 x 88,9)
175 (12,1)
175 (12,1)
300 (20,7)
—
—
Sch 10, 40
5 x 1-1/2
125 x 40
5.563 x 1.900 (141,3 x 48,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
5x 2
125 x 50
5.563 x 2.375 (141,3 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
5 x 2-1/2
125 x 65
5.563 x 2.875 (141,3 x 73,0)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
5x 3
125 x 80
3.500 x 2.375 (88,9 x 60,3)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
Sch 10, 40
6 x 1-1/4
150 x 32
6.625 x 1.660 (168,3 x 42,4)
300 (20,7)
300 (20,7)
300 (20,7)
—
—
1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approval of other pipe specifications:
UL Website - see Online Certification Directory, www.ul.com
FM Global Website - www.approvalguide.com
* See Pipe Schedule Key on pages 127-128.