  162 APPROVED PRESSURE RATINGS
 Figure 730 Grooved Outlet 1 of 7
 Pipe2 Sch.*
       Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
 O.D. Inches (mm)
   UL
   ULC
  FM
  VdS
   LPCB
  psi (bar)
   Sch 10, 40
 2 x 1-1/4
50 x 32
  2.375 x 1.660 (60,3 x 42,4)
   300 (20,7)
  300 (20,7)
 300 (20,7)
   —
  —
 Sch 10, 40
 2 x 1-1/2
50 x 40
 2.375 x 1.900 (60,3 x 48,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 2-1/2 x 1-1/4
65 x 32
 2.875 x 1.660 (73,0 x 42,4)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 2-1/2 x 1-1/2
65 x 40
 2.875 x 1.900 (73,0 x 48,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 2-1/2 x 2
65 x 50
 2.875 x 2.375 (73,0 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 3 x 1-1/4
80 x 32
 3.500 x 1.660 (88,9 x 42,4)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 3 x 1-1/2
80 x 40
 3.500 x 1.900 (88,9 x 48,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 3x 2
80 x 50
 3.500 x 2.375 (88,9 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 4 x 1-1/4
100 x 32
 4.500 x 1.660 (114,3 x 42,4)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 4 x 1-1/2
100 x 40
 4.500 x 1.900 (114,3 x 48,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 4x 2
100 x 50
 4.500 x 2.375 (114,3 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 4 x 2-1/2
100 x 65
 4.500 x 2.875 (114,3 x 73,0)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 4 x 76,1
100 x 65
 4.500 x 3.000 (114,3 x 76,1)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 4x 3
100 x 80
 4.500 x 3.500 (114,3 x 88,9)
 175 (12,1)
  175 (12,1)
 300 (20,7)
 —
  —
 Sch 10, 40
 5 x 1-1/2
125 x 40
 5.563 x 1.900 (141,3 x 48,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 5x 2
125 x 50
 5.563 x 2.375 (141,3 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 5 x 2-1/2
125 x 65
 5.563 x 2.875 (141,3 x 73,0)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 5x 3
125 x 80
 3.500 x 2.375 (88,9 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
  6 x 1-1/4
150 x 32
  6.625 x 1.660 (168,3 x 42,4)
  300 (20,7)
   300 (20,7)
  300 (20,7)
  —
   —
 1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approval of other pipe specifications:
UL Website - see Online Certification Directory, www.ul.com
FM Global Website - www.approvalguide.com
* See Pipe Schedule Key on pages 127-128.