Page 165 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 165

  APPROVED PRESSURE RATINGS 163
 Figure 730 Grooved Outlet 2 of 7
 Pipe2 Sch.*
       Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
 O.D. Inches (mm)
   UL
   ULC
  FM
  VdS
   LPCB
  psi (bar)
   Sch 10, 40
 6 x 1-1/2
150 x 40
  6.625 x 1.900 (168,3 x 48,3)
   300 (20,7)
  300 (20,7)
 300 (20,7)
   —
  —
 Sch 10, 40
 6x 2
150 x 50
 6.625 x 2.375 (168,3 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 6 x 2-1/2
150 x 65
 8.625 x 2.875 (219,1 x 73,0)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 6x 3
150 x 80
 8.625 x 3.500 (219,1 x 88,9)
 250 (17,2)
  250 (17,2)
 300 (20,7
 —
  —
 Sch 10, 40
 6x 4
150 x 100
 8.625 x 4.500 (219,1 x 114,3)
 250 (17,2)
  250 (17,2)
 300 (20,7
 —
  —
 Sch 10, 40
 81 x 2
200 x 50
 6.625 x 2.375 (168,3 x 60,3)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 81 x 2-1/2
200 x 65
 6.625 x 2.875 (168,3 x 73,0)
 300 (20,7)
  300 (20,7)
 300 (20,7)
 —
  —
 Sch 10, 40
 81 x 3
200 x 80
 6.625 x 3.500 (168,3 x 88,9)
 250 (17,2)
  250 (17,2)
 300 (20,7)
 —
  —
 Sch 10, 40
  81 x 4
200 x 100
  6.625 x 4.500 (168,3 x 114,3)
  250 (17,2)
   250 (17,2)
  300 (20,7)
  —
   —
   ISO 4200 Type D, E, and F
76,1mm x 1-1/4
65 x 32
 3.000 x 1.660 (76,1 x 42,4)
  —
 —
300 (20,7)
  —
 —
 ISO 4200 Type D, E, and F
 76,1mm x 1-1/2
65 x 40
 3.000 x 1.900 (76,1 x 48,3)
 —
  —
 300 (20,7)
 —
  —
 ISO 4200 Type D, E, and F
 76,1mm x 2
65 x 50
 3.000 x 2.375 (76,1 x 60,3)
 —
  —
 300 (20,7)
 —
  —
 ISO 4200 Type D, E, and F
 139,7mm x 2
125 x 50
 5.500 x 2.375 (139,7 x 60,3)
 —
  —
 300 (20,7)
 —
  —
 ISO 4200 Type D, E, and F
 139,7mm x 76,1mm
125 x 65
 5.500 x 3.000 (139,7 x 76,1)
 —
  —
 300 (20,7)
 —
  —
 ISO 4200 Type D, E, and F
 165,1mm x 1-1/4
150 x 32
 6.500 x 1.660 (165,1 x 42,4)
 —
  —
 300 (20,7)
 —
  —
 ISO 4200 Type D, E, and F
 165,1mm x 1-1/2
150 x 40
 6.500 x 1.900 (165,1 x 48,3)
 —
  —
 300 (20,7)
 —
  —
 ISO 4200 Type D, E, and F
  165,1mm x 2
150 x 50
  6.500 x 2.375 (165,1 x 60.3)
  —
   —
  300 (20,7)
  —
   —
 1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approval of other pipe specifications:
UL Website - see Online Certification Directory, www.ul.com
FM Global Website - www.approvalguide.com
* See Pipe Schedule Key on pages 127-128.