Page 167 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 167
APPROVED PRESSURE RATINGS 165
Figure 730 Grooved Outlet 4 of 7
Pipe2 Sch.*
Nominal Pipe Size
Rated Pressure
ANSI Inches DN
O.D. Inches (mm)
UL
ULC
FM
VdS
LPCB
psi (bar)
EN 10255 Heavy
165,1mm x 1-1/2
150 x 40
6.500 x 1.900 (165,1 x 48,3)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Heavy
165,1mm x 2
150 x 50
6.500 x 2.375 (165,1 x 60.3)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Heavy
165,1mm x 76,1mm
150 x 65
6.500 x 3.000 (165,1 x 76,1)
300 (20,7)
—
300 (20,7)
—
—
EN 10255 Heavy
165,1mm x 3
150 x 80
6.500 x 3.500 (165,1 x 88,9)
—
—
300 (20,7)
—
—
EN 10255 Heavy
165,1mm x 4
150 x 100
6.500 x 4.500 (165,1 x 114,3)
—
—
300 (20,7)
—
—
EN 10255 Medium
76,1mm x 1-1/4
65 x 32
3.000 x 1.660 (76,1 x 42,4)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Medium
76,1mm x 1-1/2
65 x 40
3.000 x 1.900 (76,1 x 48,3)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Medium
76,1mm x 2
65 x 50
3.000 x 2.375 (76,1 x 60,3)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Medium
139,7mm x 1-1/2
125 x 40
5.500 x 1.900 (139,7 x 48,3)
—
—
300 (20,7)
—
—
EN 10255 Medium
139,7mm x 2
125 x 50
5.500 x 2.375 (139,7 x 60,3)
—
—
300 (20,7)
—
—
EN 10255 Medium
139,7mm x 76,1mm
125 x 65
5.500 x 3.000 (139,7 x 76,1)
300 (20,7)
—
300 (20,7)
—
—
EN 10255 Medium
139,7mm x 3
125 x 80
5.500 x 3.500 (139,7 x 88,9)
—
—
300 (20,7)
—
—
EN 10255 Medium
165,1mm x 1-1/4
150 x 32
6.500 x 1.660 (165,1 x 42,4)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Medium
165,1mm x 1-1/2
150 x 40
6.500 x 1.900 (165,1 x 48,3)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Medium
165,1mm x 2
150 x 50
6.500 x 2.375 (165,1 x 60.3)
250 (17,2)
—
300 (20,7)
—
—
EN 10255 Medium
165,1mm x 76,1mm
150 x 65
6.500 x 3.000 (165,1 x 76,1)
300 (20,7)
—
300 (20,7)
—
—
EN 10255 Medium
165,1mm x 3
150 x 80
6.500 x 3.500 (165,1 x 88,9)
—
—
300 (20,7)
—
—
EN 10255 Medium
165,1mm x 4
150 x 100
6.500 x 4.500 (165,1 x 114,3)
—
—
300 (20,7)
—
—
ISO 65 Medium
60,3mm x 42,4mm
50 x 32
2.375 x 1.600 (60,3 x 42,4)
—
—
—
—
290 (20)
1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approval of other pipe specifications:
UL Website - see Online Certification Directory, www.ul.com
FM Global Website - www.approvalguide.com
* See Pipe Schedule Key on pages 127-128.