Page 170 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 170
168 APPROVED PRESSURE RATINGS
Figure 730 Grooved Outlet 7 of 7
Pipe2 Sch.*
Nominal Pipe Size
Rated Pressure
ANSI Inches DN
O.D. Inches (mm)
UL
ULC
FM
VdS
LPCB
psi (bar)
DIN 2448 or 2548
88,9mm x 60,3mm
80 x 50
3.500 x 2.375 (88,9 x 60,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
114,3mm x 42,4mm
100 x 32
4.500 x 1.600 (114,3 x 42,4)
—
—
—
232 (16)
—
DIN 2448 or 2548
114,3mm x 48,3mm
100 x 40
4.500 x 1.900 (114,3 x 48,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
114,3mm x 60,3mm
100 x 50
4.500 x 2.375 (114,3 x 60,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
114,3mm x 73,0mm
100 x 65
4.500 x 2.875 (114,3 x 76,1)
—
—
—
232 (16)
—
DIN 2448 or 2548
114,3mm x 88,9mm
(100 x 80)
4.500 x 3.500 (114,3 x 88,9)
—
—
—
232 (16)
—
DIN 2448 or 2548
168,3mm x 42,4mm
(150 x 32)
6.625 x 1.600 (168,3 x 42,4)
—
—
—
232 (16)
—
DIN 2448 or 2548
168,3mm x 48,3mm
(150 x 40)
6.625 x 1.900 (168,3 x 48,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
168,3mm x 60,3mm
(150 x 50)
6.625 x 2.375 (168,3 x 60,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
168,3mm x 76,1mm
(150 x 65)
6.625 x 2.875 (168,3 x 76,1)
—
—
—
232 (16)
—
DIN 2448 or 2548
168,3mm x 88,9mm
(150 x 80)
6.625 x 3.500 (168,3 x 88,9)
—
—
—
232 (16)
—
DIN 2448 or 2548
168,3mm x 114,3mm
(150 x 100)
6.625 x 4.500 (168,3 x 114,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
219,1mm x 60,3mm
(200 x 50)
8.625 x 2.375 (219,1 x 60,3)
—
—
—
232 (16)
—
DIN 2448 or 2548
219,1mm x 76,1mm
(200 x 65)
8.625 x 2.875 (219,1 x 76,1)
—
—
—
232 (16)
—
DIN 2448 or 2548
219,1mm x 88,9mm
(200 x 80)
8.625 x 3.500 (219,1 x 88,9)
—
—
—
232 (16)
—
DIN 2448 or 2548
219,1mm x 114,3mm
(200 x 100)
8.625 x 4.500 (219,1 x 114,3)
—
—
—
232 (16)
—
1. For 8 inch sizes, minimum allowed pipe wall thickness is 0.188.
2. See Agency website for Listing/Approval of other pipe specifications:
UL Website - see Online Certification Directory, www.ul.com
FM Global Website - www.approvalguide.com
* See Pipe Schedule Key on pages 127-128.