  APPROVED PRESSURE RATINGS 169
 Figure 40-5 Strap Outlet
 Pipe Sch.*
   Nominal Pipe Size
  Rated Pressure
 ANSI Inches DN
   O.D. Inches (mm)
  UL
   ULC
  FM
  VdS
  LPCB
  psi (bar)
 Schedule 10, 40
 1-1/4 x 1/2
32 x 15
 1.660 x 0.840 (42,2 x 21,3)
 175 (12,1)
  175 (12,1)
 175 (12,1)
  —
   —
 Schedule 10, 40
 1-1/4 x 3/4
32 x 20
 1.660 x 1.050 (42,2 x 26,7)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 1-1/4 x 1
32 x 25
 1.660 x 1.315 (42,2 x 33,4)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 1-1/2 x 1/2
40 x 15
 1.900 x 0.840 (48,3 x 21,3)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 1-1/2 x 3/4
40 x 20
 1.900 x 1.050 (48,3 x 26,7)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 1-1/2 x 1
40 x 25
 1.900 x 1.315 (48,3 x 33,4)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 2 x 1/2
50 x 15
 2.375 x 0.840 (60,3 x 21,3)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 2 x 3/4
50 x 20
 2.375 x 1.050 (60,3 x 26,7)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 2 x1
50 x 25
 2.375 x 1.315 (60,3 x 33,4)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 2-1/2 x 1/2
65 x 15
 2.875 x 0.840 (73,0 x 21,3)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
 2-1/2 x 3/4
65 x 20
 2.875 x 1.050 (73,0 x 26,7)
 175 (12,1)
  175 (12,1)
 175 (12,1)
 —
 —
 Schedule 10, 40
  2-1/2 x 1
65 x 25
  2.875 x 1.315 (73,0 x 33,4)
  175 (12,1)
   175 (12,1)
  175 (12,1)
  —
  —
 * See Pipe Schedule Key on pages 127-128.