Page 178 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 178

  176 APPROVED PRESSURE RATINGS
 Figure 519 Tee
  Nominal Pipe Size
 Rated Pressure
 ANSI Inches DN
   O.D. Inches (mm)
 UL
   ULC
   FM
   VdS
   LPCB
   psi bar
 1-1/4
32
 1.660 (42,4)
 —
  —
  365 (25,2)
  232 (16,0)
  290 (20,0)
 1-1/2
40
 1.900 (48,3)
   —
  —
  365 (25,2)
  232 (16,0)
  290 (20,0)
 2
50
 2.375 (60,3)
   365 (25,2)
  —
  365 (25,2)
  232 (16,0)
  290 (20,0)
 2-1/2
65
 2.875 (73,0)
   365 (25,2)
  —
  365 (25,2)
  —
  —
 76,1mm
65
  3.00 (76,1)
    365 (25,2)
   —
   365 (25,2)
   232 (16,0)
   290 (20,0)
   3
80
3.500 (88,9)
  365 (25,2)
 —
 365 (25,2)
 232 (16,0)
 290 (20,0)
 4
100
  4.500 (114,3)
    365 (25,2)
   —
   365 (25,2)
   232 (16,0)
   290 (20,0)
   139,1mm
125
5.500 (139,7)
  365 (25,2)
 —
 365 (25,2)
 232 (16,0)
 —
 5
125
 5.563 (141,3)
   —
  —
  365 (25,2)
  —
  —
 165,1mm
150
 6.500 (165,1)
   365 (25,2)
  —
  365 (25,2)
  —
  290 (20,0)
 6
150
 6.625 (168,3)
   365 (25,2)
  —
  365 (25,2)
  232 (16,0)
  290 (20,0)
 8
200
 8.625 (219,1)
    365 (25,2)
   —
   365 (25,2)
   232 (16,0)
   290 (20,0)
 
   176   177   178   179   180