  SYSTEM DESIGN 185
 Thermal Movement 2 of 4
 Nominal Pipe Size ANSI Inches DN
  Activation Force Lbs. (N)
 1-1/4
32
  35 (156)
 1-1/2
50
  45 (200)
 2
50
  70 (311)
 2-1/2
65
  100 (645)
 —
65
  110 (489)
 3
80
  145 (645)
 4
100
   240 (1068)
  Nominal Pipe Size ANSI Inches DN
  Activation Force Lbs. (N)
 5
125
  375 (1668)
 – 150
  500 (2224)
 6
150
  520 (2313)
 8
200
  880 (3914)
 10
250
  1365 (6072)
 12
300
   1915 (8518)
 2) Design the system with flexible and/or rigid couplings and allow the pipe to move in directions desired, with the use of anchors and guides if so required. With this method, it is important to ensure that movement at branch connections, changes of direction, equipment hookup, etc., will not cause damage or harmful stresses.
3) Design the system with flexible couplings utilizing the expansion/con- traction capabilities of these products. The following example illustrates this method:
• 6 inch Schedule 40 Steel Pipe, Roll Grooved, 150 foot long, anchored at each end.
• Maximum Temperature = 200°F • Minimum Temperature = 40°F
• Install Temperature = 80°F
 ANCHOR
FLEXIBLE COUPLINGS
INTERMEDIATE GUIDES