Page 190 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 190

  188 SYSTEM DESIGN
Grinnell Flexible Couplings provide for restrained joints and allow for
deflection to aid where the pipe or equipment is misaligned.
Note that flexible couplings will not accommodate both full maximum linear movement and the maximum available angular deflection concur- rently at the same joint.
 Misalignment and Deflection 1 of 2
  Design Deflection for Roll Grooved Pipe1
 Nominal Pipe Size
 Figure 705
 ANSI Inches
 DN
  O. D. Inches / (mm)
 1-1/4
 32
 1.660 (42,4)
 1.08°
 1-1/2
 40
 1.900 (48,3)
 0.94°
 2
 50
 2.375 (60,3)
 0.75°
 2-1/2
 65
 2.875 (73,0)
 0.62°
 —
 65
 3.000 (76,1)
 0.60°
 3
 80
 3.500 (88,9)
 0.51°
 4
 100
 4.500 (114,3)
 1.19°
 5
 125
 5.563 (141,3)
 0.97°
 —
 150
 6.500 (165,1)
 0.83°
 6
 150
 6.625 (168,3)
 0.81°
 8
 200
 8.625 (219,1)
 0.63°
 10
 250
 10.750 (273,1)
 0.50
 12
  300
  12.750 (323,4)
  0.42°
 1. Deflection values are for roll grooved pipe and incorporate design reduc- tions as shown on page 127.



































   188   189   190   191   192