Page 48 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 48
46
GROOVED COUPLINGS
Figure 705 Flexible Coupling 1 of 4
BC
A
Nominal Pipe Size
Max Endd Load Lbs (kN)
Max.a,b End Gap Inches (mm)
Deflectionb
ANSI Inches DN
O.D. Inches (mm)
°Per Coupling
Inches/ Foot (mm/m)
1
25
1.315 (33,7)
407 (1,81)
0.13 (3,3)
5°30'
1.16 (96,7)
1-1/4
32
1.660 (42,4)
649 (2,88)
0.13 (3,3))
4°19'
0.90 (75,0)
1-1/2
40
1.900 (48,3)
850 (3,78)
0.13 (3,3)
3°46'
0.79 (65,8)
2
50
2.375 (60,3)
1,328 (5,90)
0.13 (3,3)
3°1'
0.63 (52,5)
2-1/2
65
2.875 (73,0)
1,947 (8,66)
0.13 (3,3)
2°29'
0.52 (43,3)
76,1
65
3.000 (76,1)
2,120 (9,43)
0.13 (3,3)
2°23'
0.50 (41,7)
3
80
3.500 (88,9)
2,885 (12,83)
0.13 (3,3)
2°3'
0.43 (35,8)
108,0
100
4.250 (108,0)
4,256 (18,93)
0.25 (6,4)
3°22'
0.70 (58,3)
4
100
4.500 (114,3)
4,769 (21,21)
0.25 (6,4)
3°11'
0.67 (55,8)
133,0
125
5.250 (133,0)
6,494 (28,88)
0.25 (6,4)
2°44'
0.56 (46,7)
139,7
125
5.500 (139,7)
7,127 (31,70)
0.25 (6,4)
2°36'
0.55 (45,5)
5
125
5.563 (141,3)
7,288 (32,41)
0.25 (6,4)
2°35'
0.54 (45,0)
159,0
150
6.250 (159,0)
9,204 (40,93)
0.25 (6,4)
2°17'
0.48 (40,0)
a. b.
c.
• •
Maximum available gap between pipe ends. Minimum gap = 0
Max end gap and deflection are for cut grooved standard weight pipe. Values for roll grooved pipe are reduced by 50%.
Maximum end load are total from all loads based on standard weight steel pipe. End loads may differ for other pipe materials and/or wall thickness. Contact your TYCO Representative for details.
See Approved Pressure Ratings starting on page 128.
Refer to Technical Data Sheet TFP1820 for more information.