Page 48 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 48

  46
GROOVED COUPLINGS
 Figure 705 Flexible Coupling 1 of 4
BC
A
                                                              Nominal Pipe Size
  Max Endd Load Lbs (kN)
 Max.a,b End Gap Inches (mm)
 Deflectionb
   ANSI Inches DN
   O.D. Inches (mm)
 °Per Coupling
 Inches/ Foot (mm/m)
 1
25
  1.315 (33,7)
  407 (1,81)
  0.13 (3,3)
 5°30'
 1.16 (96,7)
 1-1/4
32
  1.660 (42,4)
  649 (2,88)
  0.13 (3,3))
 4°19'
 0.90 (75,0)
 1-1/2
40
  1.900 (48,3)
  850 (3,78)
  0.13 (3,3)
 3°46'
 0.79 (65,8)
 2
50
  2.375 (60,3)
  1,328 (5,90)
  0.13 (3,3)
 3°1'
 0.63 (52,5)
 2-1/2
65
  2.875 (73,0)
  1,947 (8,66)
  0.13 (3,3)
 2°29'
 0.52 (43,3)
   76,1
65
  3.000 (76,1)
  2,120 (9,43)
  0.13 (3,3)
 2°23'
 0.50 (41,7)
 3
80
  3.500 (88,9)
  2,885 (12,83)
  0.13 (3,3)
 2°3'
 0.43 (35,8)
 108,0
100
  4.250 (108,0)
  4,256 (18,93)
  0.25 (6,4)
 3°22'
 0.70 (58,3)
 4
100
  4.500 (114,3)
  4,769 (21,21)
  0.25 (6,4)
 3°11'
 0.67 (55,8)
 133,0
125
  5.250 (133,0)
  6,494 (28,88)
  0.25 (6,4)
 2°44'
 0.56 (46,7)
 139,7
125
  5.500 (139,7)
  7,127 (31,70)
  0.25 (6,4)
 2°36'
 0.55 (45,5)
 5
125
  5.563 (141,3)
  7,288 (32,41)
  0.25 (6,4)
 2°35'
 0.54 (45,0)
 159,0
150
   6.250 (159,0)
   9,204 (40,93)
   0.25 (6,4)
  2°17'
  0.48 (40,0)
  a. b.
c.
• •
Maximum available gap between pipe ends. Minimum gap = 0
Max end gap and deflection are for cut grooved standard weight pipe. Values for roll grooved pipe are reduced by 50%.
Maximum end load are total from all loads based on standard weight steel pipe. End loads may differ for other pipe materials and/or wall thickness. Contact your TYCO Representative for details.
See Approved Pressure Ratings starting on page 128.
Refer to Technical Data Sheet TFP1820 for more information.