Page 50 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 50

  48
GROOVED COUPLINGS
 Figure 705 Flexible Coupling 3 of 4
BC
A
                                                              Nominal Pipe Size
  Max Endd Load Lbs kN
 Max.a, b End Gap Inches (mm)
 Deflectionb
   ANSI Inches DN
   O.D. Inches (mm)
 °Per Coupling
 Inches/ Foot (mm/m)
 165,1
150
  6.500 (165,1)
  9,950 (44,25)
  0.25 (6,4)
 2°12'
 0.46 (38,3)
 6
150
  6.625 (168,3)
  10,336 (45,97)
  0.25 (6,4)
 2°10'
 0.45 (37,5)
 8
200
  8.625 (219,1)
  17,519 (77,92)
  0.25 (6,4)
 1°40'
 0.35 (29,2)
 10e
250
  10.750 (273,0)
  22,679 (100,8)
  0.25 (6,4)
 1°20'
 0.28 (23,3)
 12e
300
   12.750 (323,9)
   31,903 (141,9)
   0.25 (6,4)
  1°7'
  0.23 (19,2)
  a. b.
d.
Maximum available gap between pipe ends. Minimum gap = 0
Max end gap and deflection are for cut grooved standard weight pipe. Values for roll grooved pipe are reduced by 50%.
Maximum end load are total from all loads based on standard weight steel pipe. End loads may differ for other pipe materials and/or wall thickness. Contact your TYCO Representative for details.
e. For 10 and 12 inch sizes where VdS Approval or LPCB Certification is required, refer to Figure 707, Technical data Sheet TFP1840.
• See Approved Pressure Ratings starting on page 128.
• Refer to Technical Data Sheet TFP1820 for more information.











































   48   49   50   51   52