Page 52 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 52

  50
GROOVED COUPLINGS
 Figure 707 Heavy-Duty Flexible Coupling 1 of 2
BC A
                                                            Nominal Pipe Size
  Max End d Load Lbs (kN)
 Max.a,b End Gap Inches (mm)
 Deflectionb
   ANSI Inches DN
   O.D. Inches (mm)
 °Per Coupling
 Inches/ Foot (mm/m)
 1-1/4
32
  1.660 (42,4)
  649 (2,88)
  0.13 (3,3)
 4°19'
 0.90 (75,0)
 1-1/2
40
  1.900 (48,3)
  1,418 (6,31)
  0.13 (3,3)
 3°46'
 0.79 (65,8)
 2
50
  2.375 (60,3)
  2,215 (9,85)
  0.13 (3,3)
 3°1'
 0.63 (52,5)
 2-1/2
65
  2.875 (73,0)
  3,246 (14,4)
  0.13 (3,3)
 2°29'
 0.52 (43,3)
   76,1mm
65
  3.000 (76,1)
  2,121 (9,44)
  0.13 (3,3)
 2°23'
 0.50 (41,7)
 3
80
  3.500 (88,9)
  4,811 (21,4)
  0.13 (3,3)
 2°3'
 0.43 (35,8)
 4
100
  4.500 (114,3)
  7,952 (35,4)
  0.25 (6,4)
 3°11'
 0.67 (55,8)
 5
125
  5.563 (141,3)
  12,153 (54,1)
  0.25 (6,4)
 2°35'
 0.54 (45,0)
 165,1mm
150
  6.500 (165,1)
  9,955 (44,3)
  0.25 (6,4)
 2°12'
 0.46 (38,3)
 6
150
  6.625 (168,3)
  17,236 (76,7)
  0.25 (6,4)
 2°10'
 0.45 (37,5)
 8
200
  8.625 (219,1)
  29,213 (130,0)
  0.25 (6,4)
 1°40'
 0.35 (29,2)
 10
250
  10.750 (273,0)
  45,381 (202,0)
  0.25 (6,4)
 1°20'
 0.28 (23,3)
 12
300
   12.750 (323,9)
   63,838 (284,0)
   0.25 (6,4)
  1°7'
  0.23 (19,2)
  a. Maximum available gap between pipe ends. Minimum gap = 0
b. Max end gap and deflection are for cut grooved standard weight pipe. Values for roll
grooved pipe are reduced by 50%.
d Maximum end load are total from all loads based on standard weight steel pipe. End
loads may differ for other pipe materials and/or wall thickness. Contact your TYCO
Representative for details.
• See Approved Pressure Ratings starting on page 131.
• Refer to Technical Data Sheet TFP1840 for more information.