Page 54 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 54

  52 GROOVED COUPLINGS BC
A
 Figure 716 Flexible Reducing Coupling 1 of 2
                                                                  Nominal Pipe Size
  Max.b End Load Lbs. (kN)
 Max.a, c End Gap Inches (mm)
 Deflectionc
  ANSI Inches DN
   O.D. Inches (mm)
 oPer Coupling
  Inches/ Foot (mm/m)
 2 x 1-1/2
50 x 40
 2.375 x 1.900 (60,3 x 48,8)
 992 (4,412)
 0.13 (3,3)
 1°53’
  0.39 (32,5)
 2-1/2 x 2
65 x 50
 2.875 x 2.375 (73,0 x 60,3)
 1,550 (6,894)
 0.13 (3,3)
 1°33’
  0.32 (26,7)
 76.1mm x 2
65 x 50
 3.000 x 2.375 (76,1 x 60,3)
 1,550 (6,894)
 0.13 (3,3)
 1°34’
  0.32 (26,7)
 3 x2
80 x 50
 3.500 x 2.375 (88,9 x 60,3)
 1,550 (6,894)
 0.13 (3,3)
 1°17’
  0.27 (22,5)
 3 x 2-1/2
80 x 65
 3.500 x 2.875 (88,9 x 73,0)
 2,272 (10,106)
 0.13 (3,3)
 1°17’
  0.27 (22,5)
 3 x 76.1mm
80 x 65
 3.500 x 3.000 (88,9 x 76,1)
 2,474 (11,004)
 0.13 (3,3)
 1°17’
  0.27 (22,5)
 4 x2
100 x 50
 4.500 x 2.375 (114,3 x 60,3)
 1,550 (6,894)
 0.19 (4,8)
 2°38’
  0.55 (45,8)
 4 x 2-1/2
100 x 65
 4.500 x 2.875 (114,3 x 73,0)
 2.271 (10,101)
 0.19 (4,8)
 2°38’
  0.55 (45,8)
 4 x 76.1mm
100 x 65
 4.500 x 3.000 (114,3 x 76,1)
 2,474 (11,004)
 0.19 (4,8)
 2°38’
  0.55 (45,8)
 4 x3
100 x 80
 4.500 x 3.500 (114,3 x 88,9)
 3,367 (14,977)
 0.19 (4,8)
 2°38’
  0.55 (45,8)
 139.7mm x 4
125 x 100
 5.500 x 4.500 (139,7 x 114,3)
 5,564 (24,749)
 0.25 (6,4)
 2°38’
  0.55 (45,8)
 5 x4
125 x 100
 5.563 x 4.500 (141,3 x 114,3)
 5,566 (24,759)
 0.25 (6,4)
 2°5’
  0.44 (36,7)
 165.1mm x 4
150 x 100
 6.500 x 4.500 (165,1 x 114,3)
 4,771 (21,222)
 0.25 (6,4)
 1°50’
  0.38 (31,7)
 6 x4
150 x 100
 6.625 x 4.500 (168,3 x 114,3)
 4,771 (21,222)
 0.25 (6,4)
 1°44’
  0.36 (30,0)
 6 x5
150 x 125
 6.625 x 5.563 (168,3 x 141,3)
 7,292 (32,436)
 0.25 (6,4)
 1°44’
  0.36 (30,0)
 8 x6
200 x 150
  8.625 x 6.625 (219,1 x 168,3)
  10,341 (45,999)
  0.25 (6,4)
  1°15’
   0.26 (21,7)
  a. Maximumavailablegapbetweenpipeends.Minimumgap=0
b. Maximumpressureandendloadaretotalfromallloadsbasedonstandardweightsteelpipe.
Pressure ratings and end loads may differ on other pipe materials and/or wall thickness. Contact
your Tyco representative for details.
c. Max end gap and deflection is for cut grooved standard weight pipe.
• See Approved Pressure Ratings starting on page 134.
• Refer to Technical Data Sheet TFP1820 for more information.
   52   53   54   55   56