Page 62 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 62

  60 FLANGE ADAPTERS AC
F BED
Size 2" (DN50) - 12" (DN300)
 Figure 71 Flange Adapter 1 of 4
                                                                                       FIGURE 71 ANSI CLASS 125 AND 150
 Nominal Pipe Size
  Max
End Loada Lbs. (kN)
  Boltb
 Net Weight. Lbs. (kg)
 ANSI Inches DN
  O.D. Inches (mm)
 Size Dia. x Lg.
 Qty.
  Torque Lbs.-ft. (Nm)
 2
50
 2.375 (60,3)
 1108 (4,93)
 5/8 x 3 (M16 x 76)
 4
 110 - 140 (149 - 190)
 3.0 (1,4)
 2-1/2
65
 2.875 (73,0)
 1623 (7,22)
 5/8 x 3 (M16 x 76)
 4
 110 - 140 (149 - 190)
 5.0 (2,3)
 3
80
 3.500 (88,9)
 2405 (10,70)
 5/8 x 3 (M16 x 76)
 4
 110 - 140 (149 - 190)
 5.6 (2,5)
 4
100
 4.500 (114,3)
 3976 (17,69)
 5/8 x 3 (M16 x 76)
 8
 110 - 140 (149 - 190)
 7.0 (3,2)
 5
125
 5.563 (141,3)
 6076 (27,03)
 3/4 x 3-1/2 (M20 x 89)
 8
 220 - 250 (298 - 339)
 9.2 (4,2)
 6
150
 6.625 (168,3)
 8618 (38,33)
 3/4 x 3-1/2 (M20 x 89)
 8
 220 - 250 (298 - 339)
 10.0 (4,5)
 8
200
 8.625 (219,1)
 14,607 (64,97)
 3/4 x 3-1/2 (M20 x 89)
 8
 220 - 250 (298 - 339)
 16.6 (7,5)
 10
250
 10.750 (273,0)
 22,691 (100,93)
 7/8 x 4 (M22 x 102)
 12
 320 - 400 (434 - 542)
 21.8 (9,9)
 12
300
  12.750 (323,9)
  31,919 (141,98)
  7/8 x 4 (M22 x 102)
  12
  320 - 400 (434 - 542)
  24.2 (11,0)
  a. Maximum end load are total form all loads based on standard weight steel pipe. End loads may dif- fer on other pipe materials and/or wall thickness. Contact your TYCO Representative for details.
b. Bolts and nuts are not supplied. Flange Mating Bolts must be at least SAE J429 Grade 5 or stronger.
Bolt lengths are standard; it is the responsibility of the purchaser to verify correct length for the
intended application.
• Pressure ratings are based on pipe schedule, pipe size, and approval agency. Approved pressure
ratings start on page 137.
• Refer to Technical Data Sheet TFP1880 for more information.





   60   61   62   63   64