Page 62 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 62
60 FLANGE ADAPTERS AC
F BED
Size 2" (DN50) - 12" (DN300)
Figure 71 Flange Adapter 1 of 4
FIGURE 71 ANSI CLASS 125 AND 150
Nominal Pipe Size
Max
End Loada Lbs. (kN)
Boltb
Net Weight. Lbs. (kg)
ANSI Inches DN
O.D. Inches (mm)
Size Dia. x Lg.
Qty.
Torque Lbs.-ft. (Nm)
2
50
2.375 (60,3)
1108 (4,93)
5/8 x 3 (M16 x 76)
4
110 - 140 (149 - 190)
3.0 (1,4)
2-1/2
65
2.875 (73,0)
1623 (7,22)
5/8 x 3 (M16 x 76)
4
110 - 140 (149 - 190)
5.0 (2,3)
3
80
3.500 (88,9)
2405 (10,70)
5/8 x 3 (M16 x 76)
4
110 - 140 (149 - 190)
5.6 (2,5)
4
100
4.500 (114,3)
3976 (17,69)
5/8 x 3 (M16 x 76)
8
110 - 140 (149 - 190)
7.0 (3,2)
5
125
5.563 (141,3)
6076 (27,03)
3/4 x 3-1/2 (M20 x 89)
8
220 - 250 (298 - 339)
9.2 (4,2)
6
150
6.625 (168,3)
8618 (38,33)
3/4 x 3-1/2 (M20 x 89)
8
220 - 250 (298 - 339)
10.0 (4,5)
8
200
8.625 (219,1)
14,607 (64,97)
3/4 x 3-1/2 (M20 x 89)
8
220 - 250 (298 - 339)
16.6 (7,5)
10
250
10.750 (273,0)
22,691 (100,93)
7/8 x 4 (M22 x 102)
12
320 - 400 (434 - 542)
21.8 (9,9)
12
300
12.750 (323,9)
31,919 (141,98)
7/8 x 4 (M22 x 102)
12
320 - 400 (434 - 542)
24.2 (11,0)
a. Maximum end load are total form all loads based on standard weight steel pipe. End loads may dif- fer on other pipe materials and/or wall thickness. Contact your TYCO Representative for details.
b. Bolts and nuts are not supplied. Flange Mating Bolts must be at least SAE J429 Grade 5 or stronger.
Bolt lengths are standard; it is the responsibility of the purchaser to verify correct length for the
intended application.
• Pressure ratings are based on pipe schedule, pipe size, and approval agency. Approved pressure
ratings start on page 137.
• Refer to Technical Data Sheet TFP1880 for more information.