  62 FLANGE ADAPTERS AC
F BED
Size 2" (DN50) - 12" (DN300)
 Figure 71 Flange Adapter 3 of 4
                                                                                       FIGURE 71 PN10 AND PN16 (METRIC)
 Nominal Pipe Size
  Flange Bolt Pattern
  Max
End Loadb Lbs. (kN)
  Boltc
 Net Weight. Lbs. (kg)
 ANSI Inches DN
  O.D. (mm)
 Size Dia. x Lg.
 Qty.
  Torque Nm
 2
50
 60,3
 PN10/ PN16
  1108 (4,93)
 M16 x 76
 4
  149-190
  3.0 (1,4)
 —
65
 76,1
 PN10/ PN16
  1767 (7,86)
 M16 x 76
 4
  149-190
  5.0 (2,3)
 3a
80
 88,9
 PN10
  2405 (10,70)
 M16 x 76
 4
  149-190
  5.6 (2,5)
 3
80
 88,9
 PN16
  2405 (10,70)
 M16 x 76
 8
  149-190
  5.6 (2,5)
 4
100
 114,3
 PN10/ PN16
  3976 (17,69)
 M16 x 76
 8
  149-190
  7.0 (3,2)
 —
125
 139,7
 PN10/ PN16
  5940 (26,42)
 M16 x 89
 8
  149-190
  9.2 (4,2)
 —
150
 165,1
 PN10/ PN16
  8296 (36,90)
 M20 x 89
 8
  298-339
  10.0 (4,5)
 6
150
 168,3
 PN10/ PN16
  8618 (38,33)
 M20 x 89
 8
  298-339
  16.6 (7,5)
 8a
200
 219,1
 PN10
  14607 (64,97)
 M20 x 89
 8
  298-339
  21.8 (9,9)
 8
200
 219,1
 PN16
  14607 (64,97)
 M20 x 89
 12
  298-339
  21.8 (9,9)
 10a
250
 273,0
 PN10
  22691 (100,93)
 M22 x 102
 12
  298-339
  22.5 (10,2)
 10
250
 273,0
 PN16
  22691 (100,93)
 M22 x 102
 12
  434-542
  24.2 (11,0)
 12a
300
 323,9
 PN10
  31919 (141,98)
 M20 x 102
 12
  298-339
  27.5 (12,5)
 12
300
  323,9
  PN16
   31919 (141,98)
  M22 x 102
  12
   434-542
   28.0 (12,7)
  a. For noted sizes, PN10 and PN16 dimensional values differ.
b. Maximum pressure and end load are total from all loads based on standard weight steel pipe. Pres-
sure ratings and end loads may differ on other pipe materials and/or wall thickness. Contact your
TYCO representative for details.
c. Mating Bolts and Nuts are not supplied. Flange Mating Bolts must be at least SAE J429 Grade 5 or
stronger. Bolt lengths are standard; it is the responsibility of the purchaser to verify correct length
for the intended application.
• Pressure ratings are based on pipe schedule, pipe size, and approval agency. Approved pressure
ratings start on page 137.
• Refer to Technical data Sheet TFP1880 for more information.