Page 77 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 77
GROOVED FITTINGS 75
Figure 320 Fabricated Thread Tees Groove x Grooved x Male Thread
C to TE
C to GE
Nominal Size ANSI DN
Pipe
O.D. Inches (mm)
Figure 519
Nominal C to GE Inches (mm)
Nominal C to TE Inches (mm)
Approx. Weight Lbs. (kg)
1
25
1.31 (33.4)
2.25 (57,2)
2.25 (57,2)
1.3 (0,6)
1-1/4
32
1.66 (42,4)
2.75 (69,9)
2.75 (69,9)
1.5 (0,7)
1-1/2
40
1.90 (48,3)
2.75 (69,9)
2.75 (69,9)
1.9 (0,9)
2
50
2.37 (60,3)
3.25 (82,6)
4.25 (108,0)
3.2 (1,5)
2-1/2
65
2.87 (73,0)
3.75 (95,3)
3.75 (95,3)
4.0 (1,8)
76,1mm
65
3.00 (76,1)
3.75 (95,3)
3.75 (95,3)
4.5 (2,0)
3
80
3.50 (88,9)
4.25 (108,0)
6.00 (152,4)
6.0 (2,7)
4
100
4.50 (114,3)
5.00 (127,0)
7.25 (184,2)
11.0 (5,0)
139,1mm
125
5.50 (139,7)
5.50 (139,7)
5.50 (139,7)
21.0 (9,5)
5
125
5.56 (141,3)
5.50 (127,0)
5.50 (139,7)
23.0 (10,5)
165,1mm
150
6.50 (165,1)
6.50 (165,1)
6.50 (165,1)
25.0 (11,3)
6
150
6.63 (168,3)
6.50 (165,1)
6.50 (165,1)
28.0 (12,7)
8
200
8.63 (219,1)
7.75 (196,9)
7.75 (196,9)
38.7 (17,6)
10
250
10.75 (273,0)
9.00 (228,6)
9.00 (228,6)
72.1 (32,8)
12
300
12.75 (323,9)
10.00 (254,0)
10.00 (254,0)
92.5 (42,0)
• Refer to Technical Data Sheet TFP1815 for more information.