Page 92 - Tyco-Grooved-Fire-Protection-Products-Installation-Handbook
P. 92

  90
GROOVED FITTINGS
 Figure 350 & 550 Concentric Reducers 2 of 5
E to E
FIGURE 350 FABRICATED CONCENTRIC REDUCER
E to E
FIGURE 550 CAST CONCENTRIC REDUCER
                           Nominal Pipe Size
 Figure 350 Fabricated
  Figure 550 Cast
 ANSI Inches DN
 Pipe O.D. Inches (mm)
 E to E Inches (mm)
  Approx. Weight Lbs. (kg).
  E to E Inches (mm)
  Approx. Weight Lbs. (kg).
  3 x 1-1/4
80 x 32
  3.50 x 1.66 (88,9 x 42,4)
   2.50 (63,5)
  1.3 (0,6)
  —
  —
 3 x 1-1/2
80 x 40
 3.50 x 1.90 (88,9 x 48,3)
 —
  —
  2.50 (63,5)
  1.8 (0,8)
 3 x2
80 x 50
 3.50 x 2.37 (88,9 x 60,3)
 —
  —
  2.50 (63,5)
  1.7 (0,8)
 3 x 2-1/2
80 x 65
  3.50 x 2.87 (88,9 x 73,0)
  —
   —
   2.50 (63,5)
   1.7 (0,8)
  3 x 76,1mm
80 x 65
 3.50 x 3.00 (88,9 x 76,1)
  —
 —
 2.50 (63,5)
 2.0 (0,9)
 4 x1
100 x 25
 4.50 x 1.31 (114,3 x 33,4)
 3.00 (76,2)
  2.9 (1,1)
  —
  —
 4 x 1-1/4
100 x 32
 4.50 x 1.66 (114,3 x 42,4)
 3.00 (76,2)
  2.2 (1,0)
  —
  —
 4 x 1-1/2
100 x 40
 4.50 x 1.90 (114,3 x 48,3)
 3.00 (76,2)
  2.3 (1,0)
  —
  —
 4 x2
100 x 50
 4.50 x 2.37 (114,3 x 60,3)
 —
  —
  3.00 (76,2)
  2.4 (1,1)
 4 x 2-1/2
100 x 65
  4.50 x 2.87 (114,3 x 73,0)
  —
   —
   3.00 (76,2)
   2.7 (1,2)
  4 x 76,1mm
100 x 65
 4.50 x 3.00 (114,3 x 76,1)
  —
 —
 3.00 (76,2)
 3.2 (1,5)
 4 x3
100 x 80
  4.50 x 3.50 (114,3 x 88,9)
  —
   —
   3.00 (76,2)
   2.8 (1,3)
  139,7mm x 3
(125 x 80)
 5.50 x 3.50 (139,7 x 88,9)
  —
 —
 3.50 (88,9)
 4.2 (1,9)
 139,7mm x 4
(125 x 100)
  5.50 x 4.50 (139,7 x 114,3)
  —
   —
   3.50 (88,9)
   4.4 (2,0)
  • •
Pressure ratings are based on pipe schedule, pipe size, and approval agency. Approved pressure ratings for Figure 350 start on page 169.
Refer to Technical Data Sheet TFP1815 for more information.
   90   91   92   93   94